ABB AO895 3BSC690087R1 Analog Output Module
| Brand | ABB |
| Model Number | AO895 |
| Order Number | 3BSC690087R1 |
| Unit Price | $1000 |
| Country Of Origin | Sweden and Switzerland |
| Weight | 0.35KG |
| Certificate |
C/O from the Chamber of Commerce C/Q from the manufacturer |
| Warranty | 12 Months |
| Inventory Qty | 2 |
ABB AO895 3BSC690087R1 is a Analog Output Module, it has has 8 channels and includes Intrinsic Safety protection components and a HART interface on each channel for connection to process equipment in hazardous areas without the need for additional external devices.
BB AO895 Key parameters
|
Parameter |
Specification |
|
Signal specification |
4...20 mA |
|
Number of channels |
8 |
|
Signal type |
Unipolar single ended |
|
Dielectric test voltage |
500 V a.c. |
|
Mechanics |
S800 |
Account Number 88800006406771
Account name Vogi International Trading Co., Limited
(* If the account name exceeds the available space, please continue in the address field.)
SWITF/BIC Code WIHBHKHHXXX
Bank name OCBC Hong Kong Branch
Bank address 161 Queen's Road Central, Central, Hong Kong
Country/Region Hong Kong (China)
Account type Business Account
Bank code 035
Payment method For the payment of goods, please make a FPS/CHATS/SWIFT Payment
Notes Please include the following memo/message to receiver when making a payment: [Buyer Name] [Invoice/Contract Number] [Product]
ABB AO895 Features and Benefits
8 channels of 4...20 mA outputs.
HART communication.
1 group of 8 channels isolated from ground.
Power to drive Ex certified I/P actuators.
The AO895 Analog Output Module has 8 channels. The module includes Intrinsic Safety protection components and a HART interface on each channel for connection to process equipment in hazardous areas without the need for additional external devices.
Each channel can drive up to 20 mA loop current into a field load such as an Ex-certified current-to-pressure converter and is limited to 22 mA in overload conditions. All eight channels are isolated from the ModuleBus and power supply in one group. Power to the output stages is converted from the 24 V on the power supply connections.