Bently Nevada 136188-02 Ethernet /RS485 Modbus I/O Module – Vogi international

Vogi international

Bently Nevada 136188-02 Ethernet /RS485 Modbus I/O Module

Brand Bently Nevada
Module Number 136188-02
Unit Price $1000
Country Of Origin USA
Weight 0.44kg
Certificate C/O from the Chamber of Commerce
C/Q from the Manufacturer
Warranty 12 Months
Inventory Qty 25

Bently Nevada 136188-02 is an Ethernet/RS485 Modbus I/O module designed for Bently Nevada 3500 series machinery protection systems. It integrates Ethernet TCP/IP and serial communication (RS232/RS422/RS485) capabilities to seamlessly transmit real-time vibration, temperature, displacement and other monitoring data of rotating machinery to DCS, PLC or SCADA systems for predictive maintenance and process control.

Bently Nevada 136188-02 Key parameters

Category

Specification

Model

Bently Nevada 136188-02

Product Type

Ethernet/RS485 Modbus I/O Module

Communication Interfaces

Ethernet (RJ-45), Serial (RS232/RS422/RS485)

Supported Protocols

Modbus TCP/IP, Modbus RTU, Bently Nevada Protocol

Ethernet Speed

10 Mbps (IEEE 802.3 compliant)

Modbus Registers

Up to 256 configurable registers

Power Consumption

5.6 W (typical with RS485)

Operating Temperature

-30°C to +65°C (-22°F to +149°F)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Humidity

95% non-condensing

Hot-Swap Support

Yes

Certifications

ATEX/IECEx, CSA/NRTL, DNV GL, ABS

Compatibility

3500/92 Communication Gateway (requires 136180-01 mainboard)

Beneficiary's Bank: CITIBANK N.A.
Beneficiary address:Champion Tower,Three Garden Road,Central,Hong Kong
Beneficiary: Vogi International Trading Co., Limited
Account No.: 395714900
Bank Code: 006 Branch Code: 391
Swift Code:CITIHKHX (CITIHKHXXXX * If 11 characters are required)
Payment Term:T/T

Bently Nevada 136188-02 Compatible products

Required Components:

3500/92 Main Module (136180-01): Must be paired with the Bently Nevada 136188-02 to provide communication protocol processing capabilities.

3500 Rack and Power Supply: Such as the 3500/05 rack frame and 3500/15 power supply module, which power the system and provide physical mounting slots.

Data Source Modules:

Vibration Monitoring: 3500/42M Proximitor Monitor (Shaft Displacement/Vibration)

Temperature Monitoring: 3500/60M Temperature Module (Bearing/Winding Temperature) Data is collected by these modules and forwarded to the control system by the Bently Nevada 136188-02.

Software Tools:

System 1™ Software: Configures the Bently Nevada 136188-02 register map and enables historical data analysis via Ethernet.

136188-02 3

Comparison with similar models and alternatives

Model Number

Interface Type

Key Differences

Applicable Scenarios

136188-02

Ethernet + RS485

Supports long-distance RS485 bus (≤500m)

Distributed multi-rack systems (e.g., refineries)

136188-01

Ethernet + RS232

RS232 limited to short-distance point-to-point (≤15m)

Local control cabinet to HMI direct connection

3500/90 (Legacy)

Serial communication only

No Ethernet support, no configurable registers

Legacy system retrofits (requires protocol gateway)

Analysis of alternative models:

Advantages: The RS485 interface of 136188-02 supports multi-node series connection (such as fan group control), and the cost is lower than the fiber optic solution; compared with 136188-01, it is more suitable for wide-area deployment such as oil and gas pipelines.

Limitations: If the host only needs RS232 communication (such as old PLC), 136188-01 is more economical; it is recommended to directly use 136188-02 for new projects to retain scalability.