1900/65A General Purpose Equipment Monitor
1900/65A-AA-BB-CC-DD-EE | |||
AA: Power Option | |||
00 | 18 to 36 Vdc | 01 | 110 to 220 Vac @ 50 to 60 Hz (external supply) |
BB: Display Option | |||
00 | No display | 01 | Attached display (no cable) |
02 | Display with 10’ PVC cable | 03 | Display with 10’ unassembled PVC cable |
04 | Display with 10’ TEF cable | 05 | Display with 10’ unassembled TEF cable |
CC: Mounting Option | |||
00 | None | 01 | DIN rail mount |
02 | Bulkhead Mount | 03 | Fiberglass NEMA 4X/IP66 WP housing with window in door |
04 | 1900/55 replacement kit | 07 | ProTIM Housing, Wiring and Mounting Hardware |


Bently Nevada 1900/65A-01-01-01 Core Function
Flexible Multi-Sensor Input Handling
The Bently Nevada 1900/65A-01-01-01 processes four transducer inputs and four temperature inputs. Each transducer channel supports accelerometers, velocity sensors, or proximity probes. Temperature inputs accept Type E/J/K/T thermo couples and 2-/3-wire RTDs, enabling comprehensive monitoring of vibration, position, and thermal parameters .
Configurable Alarm Logic & Output Control
Relay Outputs : Programmable contacts trigger based on OK/Alert/Danger statuses from any input channel or combined logic (e.g., voting schemes).
Recorder Outputs : Assign 4–20 mA signals to any measured variable for DCS/SCADA integration.
Buffered Outputs: Dedicated raw signal ports enable real-time diagnostics via portable analyzers .