The MPC4 card provides 4 dynamic channels and 2 tachometer (speed) channels, all of which are independently configurable. An MPC4 machinery protection card is installed in the front of a VM600 ABE04x rack and requires an IOC4T card to form a card pair.
VM600 MPC4 Key parameters
|
Parameter |
Specification |
|
Categories |
Centralized vibration & combustion monitoring system,VM600Mk1 Modules |
|
Number of inputs |
4 Per MPC4 card |
|
DC Range |
0 to +20V or 0 to -20V |
|
AC Range |
±10V max |
|
Common mode voltage range |
−50 to +50 V |
|
CMRR |
>60 dB at 50 Hz |
|
Crosstalk |
−72 dB |
|
Input impedance |
200 kΩ |
|
Current measuring resistor |
324.5 Ω |
Account Number 88800006406771
Account name Vogi International Trading Co., Limited
(* If the account name exceeds the available space, please continue in the address field.)
SWITF/BIC Code WIHBHKHHXXX
Bank name OCBC Hong Kong Branch
Bank address 161 Queen's Road Central, Central, Hong Kong
Country/Region Hong Kong (China)
Account type Business Account
Bank code 035
Payment method For the payment of goods, please make a FPS/CHATS/SWIFT Payment
Notes Please include the following memo/message to receiver when making a payment: [Buyer Name] [Invoice/Contract Number] [Product]
Key Features
Signal Measurement and Monitoring:
Programmable measurement and monitoring of up to four dynamic signal inputs, such as acceleration and velocity.
Monitoring of up to two velocity inputs.
Integrated Power Supply:
Provides integrated power for sensors and signal conditioners, such as IEPE accelerometers and proximity measurement systems.
System Support:
A core component of the VM600 Series Mechanical Protection System (MPS).
Supports real-time hot-swapping.
Flexible Version Selection
Available in "Standard," "Standalone Circuit," and "Safety In-Service" (SIL) versions.
Applications
Primarily used for the protection and basic condition monitoring of rotating machinery.