VM600 MPC4 machinery protection card – Vogi international

Vogi international

VM600 MPC4 machinery protection card

Module Number MPC4
Order Number MPC4 200-510-070-113 MPC4 200-510-078-115 MPC4 200-510-074-113
Unit Price $6000
Country Of Origin Switzerland
Weight 1KG
Certificate C/O from the Chamber of Commerce
C/Q from the Manufacturer
Warranty 12 Months
Inventory Qty 27

The MPC4 card provides 4 dynamic channels and 2 tachometer (speed) channels, all of which are independently configurable. An MPC4 machinery protection card is installed in the front of a VM600 ABE04x rack and requires an IOC4T card to form a card pair.

VM600 MPC4 Key parameters

Parameter

Specification

Categories

Centralized vibration & combustion monitoring system,VM600Mk1 Modules

Number of inputs

4 Per MPC4 card

DC Range

0 to +20V or 0 to -20V

AC Range

±10V max

Common mode voltage range

−50 to +50 V

CMRR

>60 dB at 50 Hz

Crosstalk

−72 dB

Input impedance

200 kΩ

Current measuring resistor

324.5 Ω

Account Number 88800006406771

Account name Vogi International Trading Co., Limited

(* If the account name exceeds the available space, please continue in the address field.)

SWITF/BIC Code WIHBHKHHXXX

Bank name OCBC Hong Kong Branch

Bank address 161 Queen's Road Central, Central, Hong Kong

Country/Region Hong Kong (China)

Account type Business Account

Bank code 035

Payment method For the payment of goods, please make a FPS/CHATS/SWIFT Payment

Notes Please include the following memo/message to receiver when making a payment: [Buyer Name] [Invoice/Contract Number] [Product]

Key Features

Signal Measurement and Monitoring:
Programmable measurement and monitoring of up to four dynamic signal inputs, such as acceleration and velocity.

Monitoring of up to two velocity inputs.

 

Integrated Power Supply:
Provides integrated power for sensors and signal conditioners, such as IEPE accelerometers and proximity measurement systems.

 

System Support:
A core component of the VM600 Series Mechanical Protection System (MPS).

Supports real-time hot-swapping.

 

Flexible Version Selection
Available in "Standard," "Standalone Circuit," and "Safety In-Service" (SIL) versions.

 

Applications
Primarily used for the protection and basic condition monitoring of rotating machinery.